Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
KYN28-24 armored withdrawable AC metal-enclosed switchgear is suitable for indoor three-phase 50/60HZ, rated voltage 24kV power systems. It is mainly used in power plants, substations, industrial and mining enterprises and high-rise buildings. Receive and distribute electrical energy and control, protect and monitor circuits.
KYN28-24 switchgear has various functions to prevent misoperation, including preventing the handcart from moving with load, preventing the grounding switch from closing the circuit breaker in the closed position, preventing the grounding switch from being powered on, and preventing accidentally entering the live compartment.
The switch equipment is equipped with VS1 and VN2 series medium-voltage AC vacuum circuit breakers and sealed vacuum switches with excellent performance. The secondary circuit of the switchgear is equipped with innovative and reliable control and protection components; the busbar adopts heat-shrinkable insulation material or oxygen-coated insulation means, the electrode shape is optimized, and the cabinet structure is compact. This switchgear is technologically innovative, has stable performance, and has a reasonable structure. Easy-to-use, safe and reliable power distribution equipment.
This product complies with GB 3906, IEC 62271-200 and other standard requirements.
KYN28-24 switchgear consists of two parts: the cabinet and the removable part (commonly known as the handcart). The cabinet is divided into multiple functional compartments with metal partitions, such as busbar room, circuit breaker room, cable room, relay instrument room, etc. The removable parts of the switchgear can be equipped with vacuum circuit breaker handcarts, voltage transformer handcarts, arrester handcarts, isolating handcarts and fuse handcarts, etc.
A,Bus room.
B,Circuit breaker handcart room.
C,Cable room.
D,Relay instrument room.
1,Secondary plug.
2,Opening and closing indication.
3,Energy storage indication.
4,Counter.
5,Opening button.
6,Closing button.
7,Manual energy storage.
8,Shake-in mechanism.
9,Transfer vehicle keyhole.
10,Transfer vehicle positioning.
11,Earthing switch.
12,Emergency unlock.
The above parameters are typical data; if the existing styles do not meet your specific demands, please contact us for a custom design.We have significant personalized customization development and production skills, allowing us to provide tailored solutions to customers all over the world.