• 40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

Customization:
Manufacturer/Factory & Trading Company
Gold Member Since 2024

Suppliers with verified business licenses

Fujian, China
to see all verified strength labels (23)

Product Description

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs
General Information

40.5kV Indoor SF6 Switch-Disconnector FL(R)N36 Load Break Switch LBS is a double-break rotary load switch using SF6 gas as the insulating and arc-extinguishing medium. It is suitable for 35-40.5kV power distribution systems. Each switch is permanently sealed after being filled with 0.4bar pressure SF6 gas. The switch can be installed vertically or horizontally. The typical installation method in the ring main unit is to install a steel partition horizontally between the cable room and the busbar room. This installation method isolates the busbar from the cable joint to comply with safety requirements for operation and maintenance.

Combining the FLN36-40.5kV indoor high-voltage SF6 load switch with other electrical components can realize control and protection functions and serve as the control and protection of electrical equipment in industrial and mining enterprises, civil power supply and secondary substations. It is used to make and break load current and overload current. It can also be used to make and break no-load long lines, no-load transformers and capacitor banks. The series combination of load switch and current-limiting fuse can be used instead of a circuit breaker, that is, the load switch is responsible for closing and breaking various load currents, while the current-limiting fuse is responsible for breaking larger overload currents and short-circuit currents.

The product complies with GB3804, GB16926, IEC 60265-1 and GB16926, IEC60420 standards.

Structural Features

  1. The load switch adopts double-break, rotary movable contacts and has the following three states: closing; opening; grounding.
  2. Good insulation performance. The load switch uses SF6 as arc extinguishing and insulating medium. The switch is sealed by an upper and lower shell cast by epoxy resin.
  3. Good safety performance. If arcing occurs internally, there is a structural weak point at the rear of the enclosure that will burst open, and then the arc vent valve on the cabinet will open and direct the overpressure airflow to the outside of the cabinet.
  4. It can be operated manually or electrically, and the operation is convenient and reliable.
  5. Three-phase integral installation, good periodicity, small number of parts, easy adjustment and installation, simple and easy, and long life.
  6. Each load switch is sealed and maintenance-free for life.
  7. The load switch and operating mechanism are placed in the detachable upper unit. It is easy to change the load switch cabinet into a load switch + fuse combination electrical cabinet, or change the load switch + fuse combination electrical cabinet into a load switch cabinet. .
  8. It can be used as a compact, miniaturized, frequent operation and other places.

Operating Mechanism

The spring operating mechanism of the load switch and its combined electrical appliances is divided into single spring operating mechanism and double spring operating mechanism. The FLN36-12D load switch equipped with a single spring operating mechanism is mainly used for the incoming and outgoing line control unit. The FLRN36-12D load switch-fuse combination appliance equipped with a double spring operating mechanism is mainly used for transformer protection units.

Usage Environment

  1. Ambient air temperature: upper limit +40ºC, lower limit -15ºC.
  2. Environmental humidity: The daily average relative humidity is not greater than 95%, and the monthly average relative humidity is not greater than 90%.
  3. Altitude: The maximum altitude of the equipment installation site is 2000m.
  4. Earthquake: The earthquake intensity does not exceed 8 degrees.
  5. There is no serious pollution in the surrounding air, such as dust, smoke, chemical corrosives, flammable gases, gasoline and salt agents, etc.
  6. If you have special requirements, please indicate them when ordering.

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

Appearance Dimension Drawing

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

Arc Extinguishing and Breaking Principle

SF6 gas has good arc extinguishing performance. In order to extinguish the arc quickly, when the switch is breaking the current, an arc will be generated when the moving and static contacts are just separated. At this time, due to the magnetic field of the permanent magnet, the arc will be driven to move quickly, causing the arc to It is elongated and continuously combined with SF6 gas to be quickly dissociated and cooled. It is extinguished when the current crosses zero. The double fracture opening distance has the insulation level of isolating the fracture. Permanent magnet rotating arc principle, small operating power, strong extinguishing ability, light contact burn, and extended electrical life.

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

Installation

  1. The product is packaged in a single unit when it leaves the factory. Before unpacking, check whether it has been exposed to rain or moisture. The product should be unpacked indoors. After unpacking, you should conduct a visual inspection of the product to see if it is damaged or damp, and check whether the accompanying accessories and technical information are complete according to the packing list.
  2. After unpacking the product, dust, dirt, etc. on the product should be removed.
  3. Before the product is put into use, it should be confirmed whether the usage environment conditions are consistent with the specified requirements, otherwise measures should be taken.

Commissioning

The product has been strictly commissioned before leaving the factory. The installed product should be debugged as follows:

  1. The speed of just separating and closing should meet the requirements of the factory inspection sheet.
  2. Perform 10 closing and opening operations on the load switch and grounding switch. For those equipped with an electric mechanism, 5 closing and opening operations should be performed at the rated operating voltage each time. The action should be reliable.
  3. Use a simulated fuse to conduct an impactor opening test on the combined electrical appliance, twice for each phase. The action should be reliable, and the closing operation cannot be achieved after opening.
  4. Conduct a power frequency withstand voltage test on the product according to the parameters on the factory inspection sheet.

Usage

  1. The load switch in normal operation should be in the closing state, the grounding switch should be in the open position, and the grounding switch cannot be closed.
  2. During maintenance, the load switch should be opened first and the grounding switch can only be closed after confirming that there is no power at the cable end of the load switch.
  3. When replacing the fuse, make sure that the combined electrical appliance is automatically opened before closing the grounding switch and lower grounding knife.
  4. The fuse should be installed according to the instruction manual provided by the manufacturer. When installing, the striker of the fuse should be installed in the correct upward direction. Unless it is confirmed that a certain phase fuse does not pass the fault current, the three-phase fuse will be blown after the combination appliance automatically opens. Regardless of whether the pops out or not, all should be replaced.
  5. Load switch. When operating the combined electrical appliance, insert the handle rod into the operating hole and turn it 180 degrees clockwise to close. Otherwise, it is open. The opening of the combined electrical appliance can only be operated through the opening button.
  6. Users can install a padlock on the lock of the operating mechanism as needed to prevent misoperation.

Maintenance

Under normal use conditions where the environment meets the requirements of the installation and operation instructions, the switch body is guaranteed to be maintenance-free for 20 years. Due to environmental differences, necessary inspection and maintenance work on the load switch is still required.

  1. According to the working environment, conduct appropriate visual inspection of the insulation cover between June and December, and remove dirty and damp surfaces.
  2. Carry out lubrication and operation inspection of the operating mechanism 1 to 2 times a year to ensure normal operation. After the cumulative number of mechanical operations is 2,000 times, the performance of the mechanism should be checked.
  3. For load switches equipped with pressure gauges, the readings of the pressure gauges should be checked from time to time.
  4. When a fault current passes through the load switch fuse combination appliance and one phase fuse blows, all three phase fuses must be replaced. When replacing, the grounding switch must be closed first before replacement, and ensure that all three-phase fuses are installed in place.
  5. Users cannot arbitrarily replace electrical components that are inconsistent with the original model.
  6. Users should perform maintenance and repairs on products under the guidance of professional and technical personnel. If necessary, they can consult the manufacturer.

Switch Cabinet Display

40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs40.5kv Indoor Sf6 Switch-Disconnector FL (R) N36 Load Break Switch Lbs

Special Customization

The above parameters are typical data; if the existing styles do not meet your specific demands, please contact us for a custom design.We have significant personalized customization development and production skills, allowing us to provide tailored solutions to customers all over the world.